Product designation | SM1P | |||
Product type designation | Motor protective circuit breaker | |||
Electrical features | ||||
Number of poles | nr. | 3 | ||
Magnetic protection | Yes | |||
Thermal protection | Yes | |||
Phase failure detection | Yes | |||
Rated insulation voltage Ui | V | 690 | ||
Rated impulse withstand voltage Uimp | kV | 6 | ||
Rated frequency | Hz | 50/60 | ||
Thermal trip adjustment range | 4…6,5 | |||
Rated current (In) | A | 7 | ||
Magnetic tripping | 13 x In | |||
Operational short-circuit current breaking capacity (Ics) at AC | ||||
230V | kA | 100 | ||
400V | kA | 100 | ||
440V | kA | 100 | ||
500V | kA | 100 | ||
690V | kA | 3 | ||
Maximum short-circuit current breaking capacity (Icu) at AC | ||||
230V | kA | 100 | ||
400V | kA | 100 | ||
440V | kA | 100 | ||
500V | kA | 100 | ||
690V | kA | 3 | ||
Operations | ||||
Mechanical life | Cycles | 100,000 | ||
Electrical life | Cycles | 100,000 | ||
Mechanical feautures | ||||
Tightening torque for terminals | ||||
min | Nm | 3 | ||
max | Nm | 3 | ||
min | Ibft | 2 | ||
max | Ibft | 2 | ||
max number of wires simultaneously connectable | nr. | 2 | ||
Conductor section | ||||
AWG | ||||
min | 16 | |||
max | 8 | |||
Flexible w/o lug conductor section | ||||
min | mm² | 1 | ||
max | mm² | 10 | ||
Flexible c/w lug conductor section | ||||
min | mm² | 1 | ||
max | mm² | 10 | ||
Flexible with insulated spade lug conductor section | ||||
min | mm² | 1 | ||
max | mm² | 10 | ||
Screwdriver | PH2 | |||
Power terminal protection according to IEC/EN 60529 | IP20 | |||
Cable stripping lenght | ||||
main circuit | mm | 1 | ||
Ambient conditions | ||||
Temperature | ||||
Operating temperature | ||||
min | °C | -20 | ||
max | °C | 60 | ||
Storage temperature | ||||
min | °C | -50 | ||
max | °C | 80 | ||
Compensation temperature | ||||
min | °C | -20 | ||
max | °C | 50 | ||
Max altitude | m | 3,000 | ||
Operating position | ||||
normal | Su piano verticale | |||
allowable | Qualsiasi | |||
Mounting | A vite / profilato omega 35mm | |||
Weight | g | 350 | ||
UL technical data | ||||
Motor Disconnect | ||||
at 240V | kA | 30 | ||
at 480V | kA | 30 | ||
at 600V | kA | 30 | ||
protection | 100A class J | |||
Group Motor Installation | ||||
at 240V | kA | 30 | ||
at 480V | kA | 30 | ||
at 600V | kA | 30 | ||
protection | 100A class J | |||
Tap Conductor Protection | ||||
at 480Y/277V | kA | 50 | ||
at 600Y/347V | kA | 50 | ||
UL508 / UL 60947-4-1 Manual Self Protected Combination Motor Controller (Type E) Short circuit current | ||||
at 240V | kA | 50 | ||
at 480Y/277V | kA | 50 | ||
at 600Y/347V | kA | 50 | ||
Maximum UL/CSA horsepower ratings single-phase | ||||
at 110V-120V | hp | 1 | ||
at 220V-240V | hp | 2 | ||
Maximum UL/CSA horsepower ratings three-phase, 3-pole | ||||
at 200V-208V | hp | 3 | ||
at 220V-240V | hp | 3 | ||
at 440V-480V | hp | 10 | ||
at 550V-600V | hp | - |
2-7 zile - 5 bucata
2-7 zile - 28 bucata
2-7 zile - 64 bucata
Ai cumparat sau primit acest produs? Spune si altora parerea ta.
Avem plăcerea de a-ți prezenta programul nostru dedicat electricienilor, o oportunitate de a deveni partenerul nostru la Materiale Electrice!
Odată intrat în acest program, te vei bucura de mai multe avantaje:
Activează contul de electrician în 3 pași simpli:
Pentru a putea avea un cont de electrician pe site-ul www.materialeelectrice.ro
PASUL 2
Ne trimiți copie CIF la adresa
office@materialeelectrice.rode pe adresa cu care te-ai înregistrat.
PASUL 3
Primești un email de confirmare și te bucuri de prețurile tale speciale.